聯(lián)系 - 熱線(xiàn)
環(huán)能瓦斯發(fā)電機(jī)組機(jī)房的消防的注意事項(xiàng)有哪些?
環(huán)能瓦斯發(fā)電機(jī)組一般放在機(jī)房里,機(jī)房可布置在高層建筑、機(jī)房的首層或地下室。機(jī)房的設(shè)置有很多的事項(xiàng)需要注意。下面帶你們看一下環(huán)能瓦斯發(fā)電機(jī)組組機(jī)房的消防注意事項(xiàng)是怎樣的。
The environmental energy gas generator set is generally placed in the computer room, which can be arranged in high-rise buildings, the first floor of the computer room, or the basement. There are many things to pay attention to when setting up a computer room. Next, let me show you the fire safety precautions for the environmental energy gas generator unit room.

1、環(huán)能瓦斯發(fā)電機(jī)組房應(yīng)采用耐火極限不低于2.00h的隔墻和1.5h的樓板與其他部位隔開(kāi)。
1. The environmental energy gas generator room should be separated from other parts by partition walls with a fire resistance limit of not less than 2.00 hours and floor slabs with a fire resistance limit of 1.5 hours.
2、高層建筑內(nèi),環(huán)能瓦斯發(fā)電機(jī)組房?jī)?nèi)應(yīng)設(shè)置儲(chǔ)油間,其總儲(chǔ)油量不應(yīng)超過(guò)8.00h的需要量,或日用油箱容積不大于1m3。儲(chǔ)油間應(yīng)采用防火墻與發(fā)電機(jī)間隔開(kāi);當(dāng)必須在防火墻上開(kāi)門(mén)時(shí),應(yīng)設(shè)置能自行關(guān)閉的甲級(jí)防火門(mén)。
2. In high-rise buildings, an oil storage room should be installed in the environmental energy gas generator unit room, with a total oil storage capacity not exceeding the required amount for 8.00 hours, or a daily fuel tank capacity not exceeding 1m3. The oil storage room should be separated from the generator by a firewall; When it is necessary to open the door on the firewall, a Class A fire door that can be closed by itself should be installed.
3、環(huán)能瓦斯發(fā)電機(jī)組房布置在非高層建筑物內(nèi)時(shí),環(huán)能瓦斯發(fā)電機(jī)組房及日用油箱間耐火等級(jí)為一級(jí)。
3. When the environmental energy gas generator unit room is arranged in a non high-rise building, the fire resistance rating between the environmental energy gas generator unit room and the daily fuel tank room is level one.
4、應(yīng)設(shè)置火災(zāi)自動(dòng)報(bào)警系統(tǒng)和自動(dòng)滅火系統(tǒng)。
4. Automatic fire alarm system and automatic fire extinguishing system should be installed.
5、環(huán)能瓦斯發(fā)電機(jī)組房和控制間的照明支線(xiàn)應(yīng)接在消防配電的回路上。
5. The lighting branch lines of the environmental energy gas generator unit room and control room should be connected to the fire power distribution circuit.
6、機(jī)房?jī)?nèi)必須配備消防器材。
6. Firefighting equipment must be equipped in the computer room.
地面一層的公共建筑之中計(jì)劃建一個(gè)環(huán)能瓦斯發(fā)電機(jī)組組室,請(qǐng)問(wèn)有哪些消防規(guī)定規(guī)范?
What are the fire safety regulations and standards for building an environmental energy gas generator unit room in a public building on the ground floor?
?。?)機(jī)房外設(shè)有消防栓、消防帶、消防設(shè)施。
(1) The computer room is equipped with fire hydrants, fire hoses, and fire-fighting facilities.
?。?)機(jī)房?jī)?nèi)設(shè)有油類(lèi)滅火器干粉滅火器和氣體滅火器。
(2) There are oil fire extinguishers, dry powder fire extinguishers, and gas fire extinguishers in the computer room.
?。?)設(shè)有醒目嚴(yán)禁煙火全安圖標(biāo)、和禁止煙火文字。
(2) There are prominent safety icons prohibiting smoking and fireworks, as well as text prohibiting smoking and fireworks.
(3)機(jī)房?jī)?nèi)設(shè)有干燥沙池。
(3) There is a dry sand pit in the computer room.
?。?)與油庫(kù)要有隔離措施。
(4) Isolation measures should be taken from the oil depot.
1、可布置在建筑物的首層或地下一、二層,不應(yīng)布置在地下三層及以下。柴油的閃點(diǎn)不應(yīng)小于55℃。
1. It can be arranged on the first floor or the first or second basement level of a building, and should not be arranged on the third basement level or below. The flash point of diesel should not be less than 55 ℃.
2、環(huán)能瓦斯發(fā)電機(jī)組房應(yīng)根據(jù)防火等級(jí)選擇耐火2.00h的隔墻和1.50h的樓板與其他部位隔開(kāi)。
2. The environmental energy gas generator room should be separated from other parts by a 2.00-hour fire-resistant partition wall and a 1.50-hour floor slab according to the fire rating.
3、應(yīng)單獨(dú)設(shè)置儲(chǔ)油間,儲(chǔ)油量不超過(guò)8小時(shí)需要量,采取防泄、露油措施,油箱應(yīng)由通氣管(室外),儲(chǔ)油間應(yīng)采用防火墻與發(fā)電機(jī)間隔開(kāi);當(dāng)必須在防火墻上開(kāi)門(mén)時(shí),應(yīng)設(shè)置能自行關(guān)閉的甲級(jí)防火門(mén),設(shè)置火災(zāi)報(bào)警裝置,設(shè)置滅火設(shè)施:如氣體、泡沫、水噴霧等自動(dòng)滅火設(shè)施(滅油火)。
3. A separate oil storage room should be set up, with a storage capacity not exceeding the required amount for 8 hours. Measures should be taken to prevent leakage and oil leakage. The oil tank should be equipped with a vent pipe (outdoor), and the oil storage room should be separated from the generator by a firewall; When the door must be opened on the firewall, it shall be equipped with Class A fire doors that can be closed automatically, fire alarm devices and fire extinguishing facilities: such as gas, foam, water spray and other automatic fire extinguishing facilities (oil fire extinguishing).
在選擇機(jī)房位置時(shí)應(yīng)注意以下幾點(diǎn):
When choosing the location of the computer room, the following points should be noted:
?、俦M量靠近變配電所,這樣便于接線(xiàn)、縮短線(xiàn)纜長(zhǎng)度、減少電能損耗。
?、?Try to be as close to the substation as possible to facilitate wiring, shorten cable length, and reduce energy loss.
?、谠O(shè)置在地下一層時(shí),盡量要有一面靠外墻,以便通風(fēng)、排煙。
?、?When located on the basement level, try to have one side facing the exterior wall for ventilation and smoke exhaust.
?、蹜?yīng)注意機(jī)組的吊裝、搬運(yùn)和檢修方便。一般利用停車(chē)庫(kù)出入通道作為搬運(yùn)通道,但若通道不能滿(mǎn)足要求,要考慮預(yù)留吊裝孔。
③ Attention should be paid to the convenience of lifting, handling, and maintenance of the unit. Generally, the parking garage access channel is used as a handling channel, but if the channel cannot meet the requirements, it is necessary to consider reserving lifting holes.
消防實(shí)施的配置:
Configuration of fire protection implementation:
1、機(jī)房?jī)?nèi)必須設(shè)置有油類(lèi)滅火器干粉滅火器和氣體滅火器。
1. Oil fire extinguishers, dry powder fire extinguishers, and gas fire extinguishers must be installed in the computer room.
2、機(jī)房外設(shè)置有消防栓和消防水帶跟消防設(shè)施。
2. Fire hydrants, fire hoses, and fire-fighting facilities are installed outside the computer room.
3、并且在機(jī)房周?chē)O(shè)置醒目嚴(yán)禁煙火圖標(biāo)和禁止煙火文字。
3. And set up prominent no smoking icons and no smoking text around the computer room.
4、機(jī)房?jī)?nèi)部設(shè)置有干燥的消防沙。
4. Dry fire sand is installed inside the computer room.
5、與油房要有隔離設(shè)施。
5. There should be isolation facilities in the oil room.
6、發(fā)電機(jī)組應(yīng)當(dāng)距離建筑物和其他設(shè)備至少1米,冰保持良好的通風(fēng)。
6. The generator set should be at least 1 meter away from buildings and other equipment, and the ice should be well ventilated.
7、在機(jī)房?jī)?nèi)部有應(yīng)急照明、應(yīng)急指示,如果是地下室還要有獨(dú)立的抽風(fēng)系統(tǒng),火警裝置。
7. There are emergency lighting and emergency instructions inside the computer room. If it is a basement, there should also be an independent ventilation system and fire alarm device.
本文由 環(huán)能瓦斯發(fā)電機(jī)組 友情奉獻(xiàn).更多有關(guān)的知識(shí)請(qǐng)點(diǎn)擊 http://www.qmtg666.com/ 真誠(chéng)的態(tài)度.為您提供為全面的服務(wù).更多有關(guān)的知識(shí)我們將會(huì)陸續(xù)向大家奉獻(xiàn).敬請(qǐng)期待.
This article is a friendly contribution from Huaneng Gas Generator Unit For more related knowledge, please click http://www.qmtg666.com/ Sincere attitude To provide you with comprehensive services We will gradually contribute more relevant knowledge to everyone Stay tuned